Laserfiche WebLink
J.M. Equipment Co.Inc., Facility(11754), Used Oil Tank, 22§CCR 66265.192&STI-SP0011 November 2019 <br /> A.2 Required Venting Calculation <br /> Required Venting Calculation <br /> Tank Length, L 6.00 ft <br /> Tank Diameter, d 3.58 ft <br /> Wetted Area, A 65.71 ft^2 A _ 75rc f�` _ d£1 <br /> CFH Required 69,196.00 ft 3/hr L J <br /> CFH Available 0.00 ft^3/hr <br /> At the time of inspection, the Used Oil tank does not meet the requirements for the emergency <br /> venting capacity in accordance with API 2000 and NFPA 30. <br /> 11 <br />