J Z6 SEQUOIA ANALYTICAL <br /> 819 Striker Avenue, Suite 8 • Sacramento CA 95834 <br /> (916) 921-9600 • FAX (916) 921 0100 <br /> RESNA Industries Client Project ID #38009 04/Fire Station #2, Stockton Sampled May 25, 1993 <br /> 3164 Gold Camp Dr, Suite 200 Sample Matrix Water Received May 25, 1993 <br /> Rancho Cordova, CA 95670 Analysis Method EPA 3510/8015 Reported Jun 8, 1993 <br /> Attention Jay Johnson First Sample# 305-0919 <br /> TOTAL EXTRACTABLE PETROLEUM HYDROCARBONS <br /> Reporting Sample Sample Sample Sample Sample <br /> Analyte Limit I D I D I D I D. I D. <br /> ug/L 305-0919 305-0920 305-0921 305-0922 305-0923 <br /> W-40-MW4 W-40-MW3 W-40-MW2 W-41-MW1 W-40-RW-1 <br /> Lxtractable <br /> Hydrocarbons 50 N D 60 N D 310 73 <br /> Chromatogram Pattern HP13 HPa HPe <br /> Hydrocarbons Hydrocarbons Hydrocarbons <br /> (C20-C23) (<C12) (<C12) <br /> • <br /> Oualdy Control Data <br /> Report Limit Multiplication Factor 1 0 1 0 10 1 0 1 0 <br /> Date Extracted 6/1/93 6/1/93 6/1/93 6/1/93 6/1/93 <br /> Date Analyzed 6/1/93 6/2/93 6/11/93 6/1/93 6/2/93 <br /> Instrument Identification HP-3B HP-3B HP-31B HP-313 HP-3B <br /> Extractable Hydrocarbons are quantitated against a fresh diesel standard <br /> Analytes reported as N D were not detected above the stated reporting limit <br /> SEQUOIA ANALYTICAL <br /> Wendy Amundsen <br /> Laboratory Director 3050919 RES <2> <br />