Laserfiche WebLink
` CALTECH Environmental Laboratories <br /> O6814 Rosecrans Avenue Paramount (A 90723-3146 <br /> Telephone (562) 272-2700 Fay (562) 272-2789 <br /> QA/QC Report <br /> Method 8260B <br /> Matrix Water <br /> Date Analyzed 9114105 <br /> IDate Extracted 9114/05 <br /> Perimeters Conc ug/L Spike Recovery % Control Limits RPD <br /> LCS LCSD Added LCS LCSD Rec RPD <br /> 1,1-Dichloroethene 46 48 50 92 98 70-130 20 6 <br /> I Benzene 50 52 50 100 104 70-130 20 4 <br /> Trichloroethene 55 58 50 110 116 70-130 20 4 <br /> Toluene 57 60 50 114 120 70-130 20 6 <br /> I Chlorobenzene 48 50 50 96 1 100 70-130 1 20 4 <br /> m,p-Xylenes 119 124 100 119 124 70-130 20 5 <br /> I. LCS Laboratory Control Standard <br /> LCSD Laboratory Control Standard Duplicate <br />' RPD Relative Percent Difference of LCS and LCSD <br /> Perimeters Method Units Det <br /> Blank Limit <br /> 1,1-Dichloroethene ND ug/L 1 <br /> I Benzene ND ug/L 0 5 <br /> Trichloroethene ND ug/L 0 5 <br /> Toluene ND ug/L 05 <br /> Chlorobenzene ND U911- 0 5 <br />' m,p-X lenes ND ug/L 0 6 <br /> MTBE ND ug/L 1 <br /> TBA ND ug/L 10 <br />' DIPE ND ug/L 1 <br /> ETBE ND u IL 1 <br /> TAME ND ug/L 1 <br /> 1,2-Dichloroethane ND ug/L 0 5 <br /> EDB ND u IL 0 5 <br /> Eth (benzene ND u IL 0 5 <br /> o-X lene ND u IL 0 6 <br />' TCE ND uglL. 0 5 <br /> PCE ND uglL 0 5 <br /> ITOTALLY DEDICAI,I✓D TO cusToMEK SATISFACTION <br />