Laserfiche WebLink
Page 12 <br /> A visual inspection is also preformed daily in the boiler room. This visual inspection includes <br /> two emergency diesel pumps, any visible valves, pipes, fittings, and their respective supports <br /> and foundations. <br /> In the generator room there is a "Daily Bulk Diesel Aboveground Tank Inspection Checklist" <br /> that must be filled out during this inspection procedure. The logs are kept on record inside a <br /> binder in the Plan Operations and Maintenance office. <br /> Area B: <br /> This area is visually inspected daily. The fuel tank leak detector alarm for the UST (exempt) <br /> that includes both vapor and liquid testing, is tested daily. The 275-gallon day tank's visual <br /> inspection includes visible valves, pipes, fittings and supports. <br /> The log for this inspection can be found inside the boiler room by the entrance. At the end of <br /> the month when the sheet is full, it is then saved for record keeping inside a binder in the Plan <br /> Operations and Maintenance office. <br /> Area C: <br /> A visual inspection of this area is performed weekly. This visual inspection includes fuel levels, <br /> lubrication oil levels, cooling system, exhaust, battery, and electrical. In addition, the unit <br /> where the 250-gallon AST is located must be wiped down during the inspection. The <br /> Emergency Power Supply System is also tested for any unusual vibrations, leakage, or noise, <br /> all lights must be working properly, and controls must be accessible. <br /> The Automatic Transfer Switch transfer test is conducted weekly to ensure it is working <br /> properly. <br /> The log for all tests, procedures and visual inspections is located inside a binder in the Plan <br /> Operations and Maintenance office. <br /> Spill incidents are to be reported by site employees and logged by the Director of Plant Operations & <br /> Maintenance using the electronic incident reporting system. A brief report describing the occurrence, <br /> remedial activities and possible modifications to current operations in order to prevent a similar <br /> occurrence from happening again will be prepared. This log is available for inspection during normal <br /> business hours. <br /> 3.0 Personnel Training <br /> In accordance with§112.7(1)(3) <br /> All plant Operations and Maintenance employees that have contact with this area are trained in <br /> observation and spill prevention once each year as required by the hospital's spill plan. At minimum, <br /> Section II of this SPCC Plan is covered in the training. They are requested to submit any <br /> recommendations in prevention techniques or any other phase of the containment process. <br /> Dameron Hospital <br /> Spill Prevention Control and Countermeasure Plan <br /> June 29,2020 <br />