Laserfiche WebLink
tank. The results of the June 3, 2011 integrity test determined that no pressure loss was <br />reported during the test demonstrating that there was no breach from the inner tank into the <br />secondary containment. A copy of Tanknology's Certificate of Testing is provided as <br />Attachment 5. <br />2.11 Estimated Remaining Service Life of the Tank System <br />Apex's best professional estimate of the remaining service life of the tank system based upon <br />the findings described and documented in Sections 2.1 through 2.10 of this Report is at least <br />10-15 years. <br />Above Ground Storage Tank Professional Engineer Certification Page 7 <br />