Laserfiche WebLink
e� <br />' ITTIntegrity Tank Testing Systems, Inc. <br />July 30, 1991 <br />DLA, DDRW, SHARPE SITE <br />Environmental Office, Bldg. S-4 <br />Attn: John Guzman <br />Lathrop, California 95331 <br />PO# DLA00591P1883 <br />Site: BLDG. 380 ( e6r'� #ZZ' Z3, 2Yt <br />Following is a summary of the precision testing we recently <br />conducted on your underground storage tank. <br />Enclosed are copies of the test worksheets, graphs, and/or <br />computer summation for your submittal to the appropriate <br />governmental agency. Individual computer generated readings <br />will be forwarded as requested. <br />A tank system may be considered tight, according to the <br />current regulations if the the test results shown below do <br />not exceed 0.05 gph. If the results are beyond this <br />parameter, an unauthorized release may have occurred, and <br />you should consider taking remedial action. <br />TANK # OR <br />TANK <br />LOCATION <br />CAPACITY <br />Three <br />20,000 <br />Four <br />20,000 <br />Five <br />20,000 <br />Please contact <br />us <br />information. <br />Sincerely, <br />W. N. Savage <br />Certified Tester <br />PRODUCT <br />TEST <br />WITHIN TIGHT <br />CONTAINED <br />RESULTS <br />TANK PARAMETERS <br />Gasoline <br />-.006 <br />Yes <br />Gasoline <br />-.028 <br />Yes <br />Gasoline <br />-.008 <br />Yes <br />if you need <br />additional <br />assistance or <br />0% PUG No <br />800 262-8378 166 Ficmk West Circle Stockton, CA 95206 (209) 466-8036 <br />