Laserfiche WebLink
I <br />HUNTER ENVIRONMENTAL SERVICES, INC. <br />18350 MT. LANGLEY STREET, SUITE 101 <br />FOUNTAIN VALLEY, CA 92708 <br />800-247-9014 800-247-2186 <br />CUSTOMER: SHELL <br />ADDRESS: 2575 Country Club <br />Stockton, CA <br />TEST RESULTS SUMMARY <br />FINAL TEST RESULTS <br />TEST DATE: 9-28-87 <br />LOCATION/IDENTIFICATION NO.: 204 752 435 <br />LEAK LOKATOR RESULTS <br />SYSTEM TANK SIZE WATER LEVEL ALR <br />NO. PRODUCT GALLONS DIA/MATL INCHES INCHES GPH CONCLUSION RECOMMENDATIONS <br />1 Regular 8000 9511/ST 0 164 +.037 Tight <br />PRODUCT LINES - HYDROSTATIC PRESSURE TEST RESULTS <br />SYSTEM TYPE OF PUMP POUNDS POUNDS MINUTES PRODUCT PRODUCT CONCLUSION <br />NO. PRODUCT REMOTE SUCTION APPLIED HELD HELD LOSS CC's LOSS GPH /RESULT <br />1 Regular Red Jacket - NOT APPLICABLE - <br />NOTE: On suction systems, NEVER put more than 15 psi on any pump system. <br />DETAIL OF TEST RESULTS <br />*LEVEL - Inches from Tank Bottom to Test Level <br />ALR - Absolute Leak Rate (Measured Leak Rate - Temperature Compensation) in Gallons Per Hour <br />CONCLUSION - NFPA 329 criterion of +/- 0.05 GPA is used to certify tightness <br />• <br />This is to certify that the above tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK <br />LOKATOR according to all standard operating procedures. Those indicated as tight at full system meet the criterion <br />established by the National Fire Protection Association Pamphlet 329 for Precision Testing. <br />Tests Conducted and Certified By: Test Van No. 30 <br />Team Manager: Rudy Roessler <br />Tank Testing Specialist: Roger Renko <br />C': a 1 1987 <br />TEST <br />TIME <br />LEAK RATE TEMPERATURE <br />ABSOLUTE <br />CHECK <br />SYSTEM <br />TEST LEVEL <br />CLOCK DURATION <br />COMPENSATION <br />LEAK RATE <br />TEST <br />NO. PRODUCT <br />NO. (IN.) <br />STATE (HR -MIN) <br />CC/DIV CC/MIN DELTA of CC/MIN <br />CC/MIN GPH <br />Y/N <br />1 Regular <br />1 164 <br />9:55 31 Min <br />1.32 +13.01 +.032 +10.65 <br />+2.36 +.037 <br />N <br />*LEVEL - Inches from Tank Bottom to Test Level <br />ALR - Absolute Leak Rate (Measured Leak Rate - Temperature Compensation) in Gallons Per Hour <br />CONCLUSION - NFPA 329 criterion of +/- 0.05 GPA is used to certify tightness <br />• <br />This is to certify that the above tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK <br />LOKATOR according to all standard operating procedures. Those indicated as tight at full system meet the criterion <br />established by the National Fire Protection Association Pamphlet 329 for Precision Testing. <br />Tests Conducted and Certified By: Test Van No. 30 <br />Team Manager: Rudy Roessler <br />Tank Testing Specialist: Roger Renko <br />C': a 1 1987 <br />