Nov 09 05 11 : O4a M I Rrchitects 92594 4 81 p. 3 <br /> Buoyancy of Underground Tanks 911512005 <br /> Fiberglass Straps with Deadman Angors <br /> Deadman { Deadman <br /> Deadman Anchor Guideline Tank Diameter; Width Height <br /> Notes: <br /> Any size tank will eqrequire 2 deadmen.one each side of tank. 64" 12" 12" <br /> Each deadman shall lay parallel to tank shell and be located 84",..._ - .IT'. __ _..12_ _..._... <br /> :so that no part of the deadman shall fall under any quadrant of 96" J 12' 12" <br /> the tank. 114" 1$'" 12" <br /> Each deadman section shall have 2 anchor points 120" t8" 12" <br /> A separate attachment point shall be furnished for each strap. 126' 18" 12 <br /> If a single deadman is used between tanks,its width sha8 be 132" 24" 12" <br /> doubted in width. 144" 24" 12 <br /> All cable connections shall be tripled damped _All holddown straps shall be uniform*tightened to tank surface <br /> Deadman Anchors sha,.l be adequately reinforced with rebar to prevent breakrngi <br /> Disclaimer Statement <br /> i <br /> The attached information is supplied to you for information purposes only. �j <br /> Therefore,M dem welding Company.their officers,directors nor subsidiaries there of aoceqany 1 no <br /> jresp2nslbili for the use of this information covered within.This infomtation Is advisn only and the use <br /> of the material and methods is solely at the risk of the user. I <br /> T <br /> 2 <br />