Laserfiche WebLink
TANk]\1]LO6Y - UNDERGROUND LEAK DETECTION SYSTEM - (V3.12) Page- <br />DR CAL9311-IVE349323-05622-01 - Nov 11, 1993, 18:10 1 <br />TEST DATE <br />: Nov 11, 1993 <br />START TIME <br />: 18:10:19 <br />CLIENT <br />: BP <br />LOCATION NAME <br />: BP <br />LOCATION CODE <br />: 11193 <br />TANK CONFIGURATION <br />: Tandem <br />TANK CONTENTS <br />: PLUS/RUN <br />TANK NUMBER <br />: 01 <br />02 <br />TANK DIAMETER <br />: 92 <br />92 in <br />TANK CAPACITY <br />: 8000 <br />10000 <br />G <br />TANK MANUFACTURER <br />: <br />TANK MATERIAL <br />: Fibreglass <br />Fibreglass <br />TANK'REGISTRATION # <br />: <br />TANK DATE INSTALLED <br />INITIAL DIPPED FUEL LEVEL <br />: 70.00 <br />75.00 <br />in <br />INITIAL DIPPED WATER LEVEL <br />: 0.00' <br />0.00 <br />in <br />POST PUMPING WATER LEVEL <br />: 0.00 <br />0.00 <br />in <br />-I <br />f-4K�0<- J- !E-: 1B -T- <br />FeEE E:3UK_-T - <br />TEST INITIAL WATER LEVEL <br />: 0.00 <br />0.00 <br />in <br />TEST FINAL WATER LEVEL <br />: 0.00 <br />0.00 <br />in <br />WATER INGRESS <br />: 0.00 <br />0.00 <br />in <br />BUBBLE SIGNATURES <br />: No <br />No <br />VACU-TECT TEST RESULT <br />: Passed <br />Passed <br />COMMENTS: <br />CONCLUSION: TANKS #2 & #3 TIGHT. <br />LINE <br />#1 Passed <br />#2 <br />#3 <br />#4 <br />#5 <br />#6 <br />1L_I INA EEE -11F LELE t: 1::�-! LEE: E3 t-1 L_ -T' <br />TEST RATE <br />PRESS1R E LoggRESULT- <br />50 PSI 0.00 8PH Passed <br />CONCLUSION: LINES 2A & 3A TIGHT. <br />` <br />This test was conducted in accordance with U.S. EPA Rule 40 CFR Parts 280 and 281. <br />.01 <br />| ="^" J. ""t^ <br />TEST RATE <br />PRESSURE <br />50 PSI 0.00 GPH <br />