Laserfiche WebLink
QKWOLOGY - UNDERGROUND LEAK DETECTION SYSTEM - (V3.12) Page 14 <br />I HOU9009-IVE9002025-07903-03 - Sep 21, 1990, 11:09 <br />k& F21 I0 t -J --- -r- [=7 I!: -f- �FF- �-F E3 L -J M M 4--N F;-- Ne <br />TEST DATE : Sep 21, 1990 <br />START TIME : 11:09:41 <br />CLIENT : B P <br />LOCATION NAME : B P <br />LOCATION CODE : <br />TANK <br />CONFIGURATION <br />: Single <br />TANK <br />CONTENTS <br />: RE6.UNLEAD <br />TANK <br />NUMBER <br />: 03 <br />TANK <br />DIAMETER <br />: 92 in <br />TANK <br />CAPACITY <br />: 10000 8 <br />TANK <br />MANUFACTURER <br />: <br />TANK <br />MATERIAL <br />: Fibreglass <br />TANK <br />REGISTRATION # <br />: <br />TANK <br />DATE INSTALLED <br />INITIAL DIPPED FUEL LEVEL : 59.00 in <br />INITIAL DIPPED WATER LEVEL : 0.00 in <br />POST PUMPING WATER LEVEL : 0.00 in <br />-T- 0, 04 PC -r- Epr 1=1-y- F": E=7 10K -JK_ -T1- <br />TEST INITIAL WATER LEVEL : 0.00 in <br />TEST FINAL WATER LEVEL : 0.00 in <br />WATER INGRESS : 0.00 in <br />BUBBLE SIGNATURES : No <br />VACU-TECT TEST RESULT : Passed <br />COMMENTS: <br />CONCLUSION: UNLEADED TANK SYSTEM TESTS TIGHT PASS <br />LINE <br />#1 Passed <br />#2 <br />#3 <br />#4 <br />#5 <br />#6 <br />COMMENTS: <br />TEST RATE <br />PRESSURE OF LOSS <br />50 PSI 0.00 6PH <br />CONCLUSION: UNLEADED PRODUCT LINE TESTS TIGHT <br />This test was conducted in accordance with U.S. EPA Rule 40 CFR Parts 280 and 281. <br />PASS <br />VACU-TECT(tm) Test Number <br />