Laserfiche WebLink
AUG 2 1 2003 <br /> Triangle Environmental, Inc. I I rI NM,H' 11 rIq--.,�TH <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS S UMMA R Y SHEE T <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Conoco Phillips Co. Facility # 2705448 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test Date: 8/ 4/03 <br /> Kathy Strickland <br /> (602)728-7149 05448 <br /> Site#:2705448 Work#: 20001409 <br /> 3202 W HAMNER IN County: SAN JOAQUIN <br /> STOCKTON, CA 95209 Cross Street: HAMNER LN/KELLY DR <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br /> 1 Unleaded Plus 10008 System 4000 N/A N/A -0.011 PASS PASS <br /> 2 Unleaded Regular 10008 System 4000 N/A N/A -0.006 PASS PASS <br /> 3 Unleaded Premium 10008 System 4000 N/A N/A -0.011 PASS PASS <br /> Certified By: Technician: Tom Corcoran State Lic.#s: 02-1626 <br /> Mfgr's#: TEI-067 <br /> VR-7539 <br /> Comments: <br /> Compliance P-L/TST.Monitor was certified on 6/27/03. <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5% as required by Local,State and Federal EPA UST Technical Standards <br /> Part 280 for precision testing systems. This SB-989 secondary containment testing system exceeds the <br /> criteria for detection as required by state and local agencies. <br />