Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility® Facility # 2705448 <br /> Tank #e 2 Test Date. 8/ 4/03 <br /> Product: Unleaded Regular Work#: 20001409 <br /> Test Method: System 4000 Test Method: TLDT <br /> Capacity: 10008 Manufacturer: FE Petro <br /> Diameter(in): L/D Model: STP MLD <br /> Product Level(in): L/D Serial#: 02071078 <br /> Liquid Volume(Gals): Line Drain Back(ml): 170 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 28 <br /> Coef,of Expansion: Metering Pressure(psi): 12 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: FE Petro <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 52 <br /> Line Start Time: 9:15 AM <br /> Test Method: ULLAGE Line End Time: 9:30 AM <br /> U11ageVolume(gals.): Line Start Level: 270 <br /> Ullage Test Time: <br /> Line End Level: 265 <br /> Ullage Vacuum(psi): <br /> Line Test Rate(gph): -0.006 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 3 <br />