Laserfiche WebLink
Triangle Environmental, Inc. <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> ST TESTING S'YS'TEMS SUMARYS' EET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Tosco Marketing Co. Tosco Facility # 05448 <br /> 3550 North Central Avenue <br /> Phoenix, AZ 85012- Test Date 6/ 8/98 <br /> Carmen Tucker <br /> (602)200-4530 <br /> Facility: Work#: 460351 <br /> Tosco Facility# 05448 County: SAN JOAQUIN <br /> 3202 W HAMNER LN Cross Street: HAMNER LN/KELLY DR <br /> STOCKTON, CA 95209 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br /> 1 Unleaded Plus 7829 System 5000 0.010 PASS PASS -0.011 PASS PASS <br /> 2 Unleaded Regular 9728 System 5000 0.010 PASS PASS -0.011 PASS PASS <br /> 3 Unleaded Premium 9728 System 5000 0.010 PASS PASS -0.011 PASS PASS <br /> Certified By: Technician: James Bowen State Lic.#s: CA-97-1603 <br /> 'X e17 #: TEI-053 IFCI-98212 AZ-T00033 <br /> -0: ID-9634006 CO-0547A <br /> Comments: <br /> Compliance test ALL REQUESTED by Carmen <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5% as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. <br />