Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 05448 <br /> Tank #: 2 Test Date: 6/ 8/98 <br /> Product: Unleaded Regular Work#: 460351 <br /> Test Method: System 5000 Test Method: R.J. FTA <br /> Capacity: 9728 Manufacturer: Vaporless <br /> Diameter(in): 92 L/D Model: LD2000 <br /> Product Level(in): 46 L/D Serial#: 66213 <br /> Liquid Volume(Gals): 4864 Line Drain Back(ml): 100 <br /> Liquid Percent(%): 50.0% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 27 <br /> Coef. of Expansion: 0.000650 Metering Pressure(psi): 23 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.5 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (17): 69 New Leak Detector? No <br /> Head Pressure(psi): 1.2 ... <br /> Test Start Time: 8:45 PM .. <br /> Test End Time: 9:00 PM Test Method: TEI LT-3 <br /> Test Rate(gph): 0.010 Pump Brand: Red Jacket <br /> Test Result: PASS System Type: pressure <br /> Line Pressure(psi): 50 <br /> . . . . ........... .. . .. 7:00 PM <br /> Line Start Time: <br /> yn� <br /> Test Method: ULLAGE Line End Time: 7:15 PM <br /> UllageVolume(gals.): 4864 Line Start Level: 130 <br /> Ullage Test Time: 8:45 PM Line End Level: 120 <br /> Ullage Vacuum(psi): 1.7 Line Test Rate(gph): -0.011 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 3 <br />