Laserfiche WebLink
0 0 <br /> Triangle vi ental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 05448 <br /> Tank #: 3 Test Date: 6/ 8/98 <br /> Product: Unleaded Premium Work#: 460351 <br /> Test Method: System 5000 Test Method: R.J. FTA <br /> Capacity: 9728 j Manufacturer: Vaporless <br /> i <br /> Diameter(in): 92 j L/D Model: LD2000 <br /> Product Level(in): 37 ( j L/D Serial#: 66214 <br /> Liquid Volume(Gals): 3601 Line Drain Back(ml): 120 <br /> Liquid Percent(%): 37.0% % L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 ( Holding Pressure(psi): 26 <br /> Coef. of Expansion: 0.000650 Metering Pressure(psi): 20 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.4 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 71 New Leak Detector? No <br /> Head Pressure(psi): 1.0 <br /> Test Start Time: 9:00 PM <br /> Test End Time: 9:15 PM <br /> Test Method: TEI LT-3 <br /> Test Rate(gph): 0.010 <br /> Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 7:30 PM <br /> Line End Time: 7:45 PM <br /> Test Method: ULLAGE <br /> Line Start Level: 120 <br /> UllageVolume(gals.): 6127 <br /> Ullage Test Time: 9:00 PM Line End Level: 110 <br /> Line Test Rate(gph): -0.011 <br /> Ullage Vacuum(psi): 1.5 I � � <br /> Ullage Result: PASS Line Test Result: PASS <br /> 4 <br />