Laserfiche WebLink
K. Float and Chain Equipment: ❑ Check this box if floats and chains are not resent at this site. <br /> p <br /> ® Check this box if float and chain equipment is installed but only as <br /> secondary leak detection. <br /> This section must be completed if floats and chains are used to perform leak detection monitoring. <br /> Complete the following checklist: <br /> ®Yes ❑ No* Were all float and chain equipment properly inspected and tested for correct functionality? <br /> ®Yes ❑ No* Were all float and chain equipment certified to be working properly? <br /> * In the Section M,below,describe how and when these deficiencies were or will be corrected. <br /> L. Impact Valves: ❑ Check this box if impact valves are not installed. <br /> Complete the following checklist: <br /> ® Yes ❑ No* Were all impact valves properly inspected and tested for correct functionality? <br /> ® Yes ❑ No* Were all impact valves certified to be working properly? <br /> * In the Section M,below,describe how and when these deficiencies were or will be corrected. <br /> M. Comments: <br /> UDC#1-2 91 PRODUCT FLOAT, UDC#7-8 DIESEL AND 87 PRODUCT FLOATS NEED TO HAVE FLOAT <br /> CUP/BOWL CLEANED OUT. TRASH INSIDE THAT CAUSED FLOATS TO STICK AND NOT TRIP SHEAR VALVE. <br /> AFTER CLEANED--RETESTED AND ALL FUNCTIONED PER MANUFACTURES GUIDE LINES. <br /> Page 5 of 5 <br /> Monitoring System Certification <br />