Laserfiche WebLink
FJ <br />t;;A___TJMK_TEK 0 6 <br />Date: MAR 2, 2009 <br />Location: CRLLC #2705448 <br />3202 W. HAMMER LANE <br />Work Order # 09030201-5 <br />Contact: CHUCK SOFTICH <br />STOCKTON, CA 95209 Telephone: (253) 437-5980 <br />SUMP # <br />PRODUCT <br />87 <br />91 <br />DIESEL <br />LD TYPE Mechanical, (W)PLLD, (P)LLD <br />M <br />M <br />M <br />LD MANUFACTURER <br />FE PETRO <br />FE PETRO <br />VAPORLESS <br />LD MODEL <br />STP -MLD <br />STP -MLD <br />LD 2000 <br />LD SERIAL NUMBER <br />UNREADABLE <br />UNREADABLE <br />5071049 <br />SUMP CONDITION <br />DRY <br />DRY <br />DRY <br />RESILIENCY <br />45 ML <br />40 ML <br />60 ML <br />OPERATING PRESSURE <br />28 PSI <br />28 PSI <br />28 PSI <br />OPENING TIME <br />3 SEC <br />3 SEC <br />3 SEC <br />METERING PRESSURE <br />10 PSI <br />10 PSI <br />10 PSI <br />FUNCTIONAL ELEMENT HOLDING PRESSURE <br />12 PSI <br />12 PSI <br />12 PSI <br />LEAK RATE LD DETECTED <br />3 GPH <br />3 GPH <br />3 GPH <br />DOES LD DETECT 3 GPH LEAK RATE? <br />YES <br />YES <br />YES <br />DOES VEEDER-ROOT CONSOLE ALARM? <br />NO <br />NO <br />NO <br />LD PASS OR FAIL? <br />PASS <br />PASS <br />PASS <br />Comments: <br />Technician: MIKE LAWRENCE <br />Signature: <br />Contractor Lic. # 803705 <br />TANK-TEK ENVIRONMENTAL CORPORATION <br />607 Elmira Road, PMB 336, Vacaville, CA 95687 — Ph. (707) 446-6151 - Fax (707) 446-6192 - E-mail: tank-tek@cwnet.com <br />31828 Cercle Chambertin, Temecula, CA 92591 — Ph. (951) 699-8058 - Fax (951) 699-8059 - E-mail: drbtanktek@sdccu.net <br />