INVOICE #WS000082 TEST DATE: 11/30/94 <br /> UNDERGROUND TANK TESTERS <br /> 15870 AVENUE 288 <br /> VISALIA, CA 93292 <br /> (800) 244-1921 <br /> TANK STATUS REPORT -- ULLAGE TEST <br /> --------------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> CRISP TANK TESTING COUNTY OF SAN JOAQUIN <br /> P.O. BOX 30487 PUBLIC WORKS DEPARTMENT <br /> 1810 EAST HAZLETON AVENUE <br /> STOCKTON, CA. STOCKTON, CA. <br /> 95213 95205 <br /> CONTACT: LEONARD CRISP CONTACT: JUNE <br /> PHONE #: 209-931-1828 PHONE #: <br /> ***** COMMENT LINES ***** <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br /> TANK #1: REG UNLEADED TYPE: STEEL SN: -.15 <br /> TANK IS TIGHT. <br /> TANK #2: DIESEL FUEL 2 TYPE: STEEL SN: -.02 <br /> TANK IS TIGHT. <br /> WILLIAM E. COC <br /> Ll 9 <br /> OPERATOR: OTTL UC 97-1583 U S TEST LUHAJ____ SIGNATURE: _-_- DATE: <br />