Laserfiche WebLink
INTEGRITY TANK TESTING SERVICES <br /> P. 0. BOX 691736, STOCKTON, CA. 95269 <br /> October 20, 1993 <br /> San Joaquin County Motor Pool Site: 1801 East Hazelton <br /> Attention: Mr. Gene Gilford <br /> 0' ' <br /> 444 South Wils' n Way <br /> Stockton, Ca. 95205 <br /> Dear Mr. Gilford, <br /> Following is a summary of the precision testing we recently conducted on your <br /> underground storage at the above site: <br /> Enclosed are copies of the test worksheet, graphs, and/or computer generated <br /> summations for your submittal to the appropriate governmental agency. <br /> A tank system may be considered tight, according to the current regulations if the test <br /> results shown below do not exceed 0.05 GPH. If the results are beyond this parameter <br /> an unauthorized release may have occurred, and you should consider taking remedial <br /> action. <br /> Tank#/Location Product Contained Loss/Gain GPH Tank Tight <br /> Northeast U/L Gaso. -.028 Yes <br /> Northwest U/L Premium Gaso. Estimated 1.6 GPH NO <br /> Please note page two and worksheet <br /> Please advise if you needed additional assistance or information. <br /> Sincerely, <br /> BZU Seam" <br /> W. N. Savage <br /> Certified Tester <br /> STOCKTON (209) 4744375 TOLL FREE (800) 262-8378 <br />