Laserfiche WebLink
Testing Requirements and Schedule <br /> Balance System <br /> Test Anniversary Date: <br /> Typo of Test Pass/Fail Standard Testing Frequency <br /> TP-201.1 B (Static Torque of Minimum, 3600 Rotation Every 3 years <br /> Rotatable Phase I Adaptors) Maximum, 108 pound-inch <br /> average static torque <br /> TP-201.1 C/D (Leak Rate of Drop 0.17 cfh @ 2 inches H2O Every 3 years <br /> Tube Overfill Prevention Devices <br /> and Spill Container Drain Valves) <br /> TP-201.3 (Static Pressure) TP-201.3, Table 1 B Every 12 months <br /> TP-201.4 (Dynamic Back Pressure) 0.15 inches H20@ 20 cfh Every 12 months <br /> z 0.45 inches H20@ 60 cfh <br /> ANhh 0.95 inches H2O @ 100 cfh <br /> TP-20.1..6 (Liquid Removal) 5 milliliters/gallon Whenever there is over <br /> 100 milliliters of gasoline <br /> in the vapor hose <br /> cfh cubic feet per hour <br />