Laserfiche WebLink
Thornton & Son Electric <br /> UST Monitoring Specialist Lic. #724513 <br /> P.O. Box 360833 Milpitas, CA 95036-0833 <br /> Phone(408)946-1015 (209)834-0792 * Fax (209) 834-0795 <br /> MECHANICAL LINE LEAK DETECTOR TEST DATA SHEET <br /> C anepa Car Wash 6230 Nanz Addrm- <br /> Pacific Ave. <br /> city state 7A ('(4c Phone <br /> StocktanI CA 195207 209 478-551 S <br /> LEAK DETECTORS <br /> NO. PRomicr MAKE MODEL SE,RIAL NUMBER <br /> I UNL 87 vM1 99LD-2000 02121497 <br /> 2 UNL 89 VMI 99LD-2000 02121496 <br /> 3 UNL 92 VMI 99LD-2000 02121498 <br /> 4 DIESEL VMI 991,1 -2000 03011460 <br /> 7-1 <br /> OFFRAXING HOLDING BLEED ME WRING OPENING u;AK RATE PASS <br /> NO. PRESSURE PRESSURE BACK/I& PRF.SSURF TIME G IMI-M YES/NO <br /> I 29 s 2 91 148 29psi 2.5sec 248MLM YES <br /> 2 28psi 28 s 160 18psk_ 2.5sec 240M1,M YES <br /> 3 26psi <br /> 16psi 150 26psi 2.5sec 296 F%4LM YES <br /> 4 28 s 28psi 122 28psi 2.5sec 252MLM YES <br /> 5 <br /> Remarks. <br /> Name ftna re Date <br /> 16-30-2003 <br /> tPO'd 5660 VER 60Z NOS v9 NO1NUGH L WLS:60 E0-0T-4=)O <br />