Laserfiche WebLink
PIP Test Date: 08/01/2002 <br /> SECONDARY CONTAINMENT TEST RESULTS Work Order: 2223164 <br /> SUMP TESTS <br /> Tank or Disp Model or Diam./Width/Length Depth Start Initial Level Finish Final Pass/ <br /> Type7 # Manufacturer Material (") ( Test Method Time Level Chane Time Result Fail <br /> STP Sump SUPREME Smith Fiberglass 48" 74" Hydrostatic-VPLT 0910 11" 0.00067 0941 0.010 gph Pass <br /> STP Sump PLUS Smith Fiberglass 48" 74" Hydrostatic-VPLT 1010 11" 0.00002 1041 0.001 gph Pass <br /> STP Sump REGULAR Smith Fiberglass 48" 74" Hydrostatic-VPLT 1015 11" " 0.00097 1046 0.015 gph Pass <br /> STP Sump DIESEL Smith Fiberglass 48" 74" Hydrostatic-VPLT 0915 11" " 0.00032 0946 0.005 gph Pass <br /> Dispenser Pan 11 Bravo Steel 18" 9" Hydrostatic-VPLT 1150 4" 0.00013 1206 0.003 gph Pass <br /> Dispenser Pan 12 Bravo Steel 18" 9" Hydrostatic-VPLT 1154 4" 0.00008 1210 0.001 gph Pass <br /> Dispenser Pan 3/5 Bravo Steel 18" 9" Hydrostatic-VPLT 1302 4" " 0.00018 1318 0.004 gph Pass <br /> Dispenser Pan 17 Bravo Steel 18" 9" Hydrostatic-VPLT 1014 4" " 0.06029 1030 1.435 gph Fail <br /> Dispenser Pan 10/8 Bravo Steel 18" 9" Hydrostatic-VPLT 1213 4" " 0.00002 1229 0.001 gph Pass <br /> Dispenser Pan 7/9 Bravo Steel 18" 9" Hydrostatic-VPLT 1232 4" " 0.00016 1448 0.003 gph Pass <br /> Dispenser Pan 15/16 Bravo Steel 18" 9" Hydrostatic-VPLT 1230 4" 0.00006 1246 0.001 gph Pass <br /> Dispenser Pan 6/4 Bravo Steel 18" 9" Hydrostatic-VPLT 1304 4" " 0.00007 1320 0.001 gph Pass <br /> Dispenser Pan 13/14 Bravo Steel 18" 9" Hydrostatic-VPLT 1325 4" 0.00015 1341 0.003 gph Pass <br /> Dispenser Pan 2 Bravo Steel 18" 9" Hydrostatic-VPLT 1345 4" " 0.00029 1401 0.006 gph Pass <br /> Dispenser Pan 1 Bravo Steel 18" 9" Hydrostatic-VPLT 1346 4" 0.00013 1402 0.003 gph Pass <br /> Comments: <br />