Champion Tank Test #0059 13-Oct-04 <br /> 4 <br /> :2 0 <br /> .0 <br /> -4 <br /> 14 <br /> SUM*rnm OR HM-) <br /> Client/Operator Data Tank and Test Parameters <br /> Client: West Lane Fuels Tank Identification: South Supreme <br /> Address: 3300 West Lane Product Type: Supreme <br /> City, St: Stockton CA 95204 Tank Capacity: 5030 Gal. <br /> Telephone: Product Level: 82.12 in. <br /> Water in Tank: 0 <br /> Contractor: Champion Tank Test Water Level ATB: 0 in. <br /> Address: P.O. Box 13059 Tank Material: FG <br /> City, St: Sacramento CA 95813 Tank Manufacturer: Unknown <br /> Telephone: 916-927-1557 Load Cell S/N: 270400000100 <br /> Probe S/N: 28 <br /> Operator: Alvin L. Milburn Probe Length: 89.00 Inches <br /> Certification 2003006 Test Duration (min): 3.253 Hours <br /> Expiration Date:1/28/2005 Sample Time: 2.921 Hours <br /> Product SGU: .75 <br /> Tank#: 2 Leak Rate G/H: 0.002 Pw5—s) <br /> Tank Address: 3300 West Lane <br /> City, St: Stockton CA 95204 <br /> way- <br />