Laserfiche WebLink
DYNAMIC BACK PRESSURE TEST DATA (BLOCKAGE) TECHNICIAN: ED STEARNS <br /> Cert# Exp. <br /> Site: WEST LANE FUELS Date: 7/26/18 Time: LOAM <br /> Nozz/Fuel 20 CFH 60 CFH 100 CFH PASS/FAIL Nozz/Fuel 20 CFH 60 CFH 100 CFH PASS/FAIL <br /> Grade (.15"Water) (.45"Water) (.95"Water) Grade (.15"Water) (.45"Water) (.95"Water) <br /> .60CFH .80CFH --- --- <br /> 1 ALL .23 .37 PASS --- <br /> 2 ALL .23 .35 PASS --- <br /> 3 ALL .25 ,36 PASS --- <br /> 4 ALL .24 .35 PASS --- <br /> 5 ALL .25 .36 PASS --- <br /> 6 ALL .25 .38 PASS --- <br /> 7 ALL .27 .36 PASS ` --- <br /> 8 ALL .24 .34 PASS r --- <br /> LIQUID REMOVAL CHECK **See Long Form Test Report for Wet Failure Testing Blockage Tester Integrity: <br /> D=Dry 1 .50"w.c.A 5 minutes PASS <br /> l ®DRY ❑DRY ❑DRY []DRY []DRY []DRY ❑DRY ❑DRY []DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> 2 ®DRY []DRY []DRY ❑DRY ❑DRY []DRY ❑DRY ❑DRY ❑DRY <br /> Int ml ml ml ml ml ml ml ml <br /> []DRY []DRY []DRY ❑DRY []DRY []DRY []DRY []DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> ❑DRY ❑DRY ❑DRY ❑DRY ❑DRY ❑DRY ❑DRY ❑DRY ❑DRY <br /> ml ml ml ml ml ml ml ml ml <br /> ® Job Complete Repairs Done to Pass Test: <br /> ❑ Not Complete -Repairs Still Needed: <br /> Parts: None Drop Tube rings Fill Adaptor Gaskets Hoses Whip Hose <br /> Nozzles Breakaways PV Valves Others: <br />