Laserfiche WebLink
416 2"d Street <br /> x' Galt, CA 95632 <br /> "'- — (209) 744-0113 Fax (209) 744-0116 <br /> E.O.VR-204 <br /> Veeder-Root In-Station Diagnostics Balance Vapor Flow Meter Operability Test Procedure <br /> Permit Number:N-945 Date of Test: 7/26/18 Time: <br /> Site Name: WEST LANE FUELS <br /> Site Address: 3300 WEST LANE <br /> City: STOCKTON, CA Zip: 95204 Technician: Ed Stearns <br /> VST: 3000490996 <br /> District: SJVAPCD Veeder-Root: A31048 <br /> Calibration Date: 7/2/18 <br /> 35424 1-2 61.902 69.202 7.300 17,00 18,00 1.00 7.481 2.419 Pass <br /> 35425 34 35.43 41.77 6.340 18.00 19.00 1.00 7.481 6.643 Pass <br /> 20124 5-6 93.80 101.03 7.230 19.00 20.00 1.00 7.481 3.355 Pass <br /> 33850 7-8 22.77 28.35 6.570 20.00 21.00 1.00 7.481 12.17 Pass <br /> ISD_Difference gallons —Gas_Flow_Meter_DifferencegQ��o, , <br /> Gallons=Cubic Feet x 7.481 %Dierence= g x 100 ® G <br /> Gas_Flow_Meter_Difference r <br /> I declare, under penalty ofperjury under the laws of the state of California that based on information and belief formed after reasonable inq y lie <br /> statements and information provided in this document are true, accurate, and complete. r <br /> cc <br /> Signature of Technician: 't T rte-^' Date: 7/26/18 <br /> vel 1 1 f, <br />