Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer ❑Industry Standard [1 Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure X Vacuum I Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauge in Hg. Equipment Resolution: - %i"x-30"Hg. <br /> Tank# 1&2 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' No <br /> Tank Capacity: 15K Split 10/5 <br /> Tank Material: Plas/Steel <br /> Tank Manufacturer: K&T Steel RECEIVED <br /> Product Stored: Regular 87/Super 91 <br /> Wait time between applying5 Minutes DEC 2 1 2011 <br /> vacuum and starting test: <br /> Test Start Time: 11:30 ENVIR1 -N"hAL HEALTH <br /> T <br /> Initial Reading(Ri): -10"Hg. 1)EPf® Z7rN1ENT <br /> Test End Time: 12:30 <br /> Final Reading(RF): -10"Hg. <br /> Test Duration: 1 Hour <br /> Change in Reading(RF-RI): 0"Hg. <br /> Pass/Fail Threshold or Criteria: No loss in Hg. <br /> Test Result: Pass <br /> Was sensor removed for testing? No <br /> Was sensor properly replaced and NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Tank is a Two Compartment Single Annular, 10K Regular 87& SK Super 91. <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. (California Code of Regulations,Title 23,Section 2637(a)(6)) <br />