Laserfiche WebLink
CAPACITY 10000 g PRECISION UNDERGROUND TANK TESTING RESULTS Patent Pending <br />TANK # Supreme PAGE 5 <br />STAT # 94183 TEST PROCEDURES <br />TEST DATE: 08/17/89 Copyright 1985 <br />NDE TECHNOLOGY, INC. PROPRIETARY <br />1. Piping Pressure Test - Yes <br />2. Pneumatic Pressure Data <br />Amount of pressure applied <br />to system: 50 PSI <br />3. Amount of pressure drop if any: 0 <br />4. Amount • time elapsed during the test 10 minutes <br />5. Piping Pressure Test Leak Rate is N112 <br />If computer is used see computer printout of leakage rate and all <br />test parameters on Test Results, Part IV, Page 11, 12 <br />Test results of storage systems that utilize pressurized piping <br />systems will not be recognized unless the turbine pump is <br />activated after the completion of a successful system test <br />6. Was turbine pump activated? Yes <br />7. Pressure piping systems shall be tested under actual, operating <br />pressures, and statement describing results must be included. <br />See *1 Above <br />8. If applicable, has the isolation procedure in addition to the <br />product line been completed? N/A <br />NDE TECHNOLOGY, INC. PROPRIETARY <br />WATT INC. 3131 FAIRHAVEN DRIVE, BAKERSFIELD, CA 93308 (805) 322-9827 <br />