Laserfiche WebLink
• PROFESSIONAL TANK SERVICES, LTD. 1912 Raymond Drive Northbrook, IL 60062 (312) 291-0113 <br />al .■ <br />1 <br />all <br />oils, �■ <br />u■ _.u■ <br />'_"""""'• September 17, 1986 <br />Chevron U.S.A., Inc. <br />2 Annabel Lane Suite 200 <br />San Ramon, Ca. 94583 <br />Re: Tank system testing 09-10-86 <br />Chevron Sta #4183 <br />236 N. Ham Lane <br />Lodi, Ca. <br />Dear Tony Arado: <br />DEC y 6 <br />ENVIROMENTAL HEALTH <br />PERMIT/SERVICES <br />The tank systems tested at this location are identified as <br />follows: <br />Tank system #1 East <br />Tank system #2 Center <br />Tank system #3 West <br />10,000 Gallon Regular. <br />10,000 Gallon Unleaded <br />5,000 Gallon Premium. <br />The National Fire Protection Association's criteria for a tight <br />tank system is a system with a rate of leak less than .050 <br />gal/hr. These are calculated, mathematical tolerances only and <br />are not meant to indicate the permission of any leak. <br />During the stand -pipe test procedure the liquid hydrostatic pres- <br />sure applied to the underground tank system is generally two to <br />three times greater than normal liquid storage pressures. This <br />increase in hydrostatic pressure will amplify the indicated rate <br />of leak accordingly. <br />Tank #1 showed a leak rate of -.024 gal/hr. <br />Tank #1 is tight. <br />Tank #2 showed a leak rate of -.028 gal/hr. <br />Tank #2 is tight. <br />Tank #3 showed a leak rate of -.003 gal/hr. <br />Tank #3 is tight. <br />Precision Tank Te <br />stinginued on page 2 <br />Professional Tank Services, Ltd. • Safe • Secure • Systematic <br />