Installation Guide 0 <br /> Test of the Leak Detector <br /> • If flow is restricted to about 3 gpm (11 Ipm)or less with the nozzle open,the leak <br /> detector has not opened.Repeat Step 8a with increased running time of pump to <br /> insure the purging of all air.All air must be purged from the system or the leak detector <br /> will restrict flow to about 3 gpm. <br /> 9. Affix the enclosed decals to the dispenser dial glass on grade of gasoline upon which the leak detector is <br /> being installed.Additional decals are available;call customer service at 1-800-873-3313 and request P/N <br /> 046-200-1. <br /> 10. Inspect all threaded joints to assure they are tight and not leaking. <br /> Test of the Leak Detector <br /> U.S.Environmental Protection Agency(EPA)regulations require annual verification of operation of leak <br /> detector.To assure maintenance of leak detection capability.Red Jacket requires that operation of the <br /> - - --- - - -mechanical leak detector be verified by testing upon start-up and that testing of the leak detector be <br /> performed routinely,at least annually. <br /> ELI L911 ON Test procedure options for mechanical leak detectors are explained in Red Jacket <br /> Engineering Reports, RJ20 and RJ21.The Red Jacket Snap Tap Connectors allow the <br /> FX2V/FX2DV leak detector to be tested with the FXV Snap Tap Tester as an option to <br /> the above test methods.See Red Jacket literature#042=111-1 for test instructions <br /> using Snap Tap Connectors. <br /> - - 11._The top cover onthe RedJacket leakdetectorisdesignedto accommodate-a sealing wire which can be <br /> usedto discourage tampering of the unauthorized removal of leak detector.(see Figure 4). <br /> • ° If the dispensing system(the solenoid valve and the nozzle)is opened previous to the <br /> completion of the line test;the FXV Series will detect this opening as a leak and <br /> restricted flow will result.Closing of the nozzle(s)for a period of time adequate to allow <br /> completion of the,line_test will allow the leak detector_to open.Once opened,full pump <br /> flow can be provided. <br /> FX2V/FX2DV <br /> Tethered cap O <br /> Sealing wire J <br /> Snap Tap © (provided by <br /> 45°elbow contractor)_ - o <br /> 1/4-inch <br /> T-fitting <br /> SIDE VIEW TOP VIEW o <br /> Vent tube <br /> Figure 4.Installing FXV in the Standard pump <br /> 6 <br />