S A N,►10 A Q U I N Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank.Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> FLAMES LIQUOR 1301 W KETTLEMAN LN, LODI March 26,2018 <br /> UST.System Observations, <br /> 319 CCR 2635(b) No spill bucket,failed to contain five gallons,or failed to provide a means to keep it empty ❑V ❑R ❑COS <br /> 320 CCR 2635(b)(2) Overfill prevention system not present or failed to meet overfill requirements ❑V o R ❑COS <br /> 321 CCR 2635(b)(2) Overfill prevention was overridden c V o R '❑COS <br /> 322 HSC 25281.6(a) Unburied below grade emergency generator system failed to meet exemption status ❑V o R ❑COS <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status ❑V c R ❑COS <br /> 324 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V o R ❑COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored o V ❑R o COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements ❑V o R o COS <br /> 329 HSC 25298 Failed to comply with all permanent closure requirements ❑V ❑R ❑COS <br /> 330 CCR 2636(f)(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system ❑V ❑R ❑COS <br /> 331 CCR 2630(d) Secondarily contained piping not maintained to allow liquid to drain into sump ❑V o R ❑COS <br /> 332 CCR 2631(b),2631(d) Primary and/or secondary containment not constructed in accordance with the established standards ❑V o R o COS <br /> Single-Walled Non-Pressured Piping r u: <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve ❑V o R o COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V ❑R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) o V o R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R 13 COS <br /> kSUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINQR-Notice to Comply) ; <br /> Item# Remarks <br /> 309 CCR 2636(f)(1) Monitoring in sump/UDC failed to activate an audible and visual alarm or stop the flow product. <br /> The 91-product in Bravo box float and chain in dispenser 1/2 UDC sump, and 87-product Bravo float and chan in <br /> UDC 3/4 failed to stop the flow of product at the dispenser when tested. All monitoring equipment shall be <br /> maintained to activate an audible and visual alarm or stop the flow of product at the dispenser when it detects a <br /> leak. The service technician adjusted the chain(s)and verified functionality. <br /> This was corrected on site. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Please be aware that as of January 1, 2014, facility operators are required to upload the following UST program <br /> documents into the California Environmental Reporting System (CERS): UST Monitoring Site Plan, UST <br /> Certification of Financial Responsibility, UST Response Plan, UST Letter from Chief Financial Officer(if <br /> FA0000392 PR0231342 SC001 03/26/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 3 of 4 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />