Laserfiche WebLink
FacilityisNot Equipped With 8. SPILL/OVERFILL CONTAINMENA'BOXEN <br />verfill Containment Boxes ❑ <br />Spilt/Overfill Containment Boxes are Present, but were Not Tested [I <br />Test Method Developed By: [I Spill Bucket Manufacturer g Industry Standard 0 Professional Engineer <br />0 Other (Specify} <br />Test Method Used: 0 Pressure 0 Vacuum 0 Hydrostatic <br />El Other (Specify) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br />Bucket Diameter: <br />77 <br />Fill Spill Box H 87 <br />Fill Spill Box 4 91 <br />12" <br />12" <br />Bucket Depth: <br />101, <br />101, <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min. <br />10 min. <br />Test Start Time: <br />9:29 am <br />9:29 am <br />Initial Reading (R,)- <br />4.0978 <br />5.8288 <br />Test End Time: <br />9:44 am <br />9:44 am <br />Final Reading (RF): <br />4.0971 <br />5.8278 <br />`rest Duration: <br />15 min. <br />15 min. <br />Change in Reading (RR,) <br />0.0007 <br />0.0010 <br />Pass/Fail Threshold or <br />Criteria: <br />+1-0.002" <br />+/-0.002" <br />Lj!Lt Resuft-, <br />M Pass 0 Fail <br />_0 Pass 0 Fail <br />Comments — (include information on repairs made rior to testin ,and recommended allow -u or ailed tests} <br />