Laserfiche WebLink
Test Date: 04/22/2003 <br /> .fpp Tankwkgy Work Order. 2226131 <br /> SUMP TESTS SECONDARY CONTAINMENT TEST RESULTS <br /> Type Tank or Disp Manufacturer Model or Diam./Width/Length Depth Test Method Start Initial Level Finish Final Pass/ <br /> # Material (") (") Time Level Change Time Result Fail <br /> STP Sump REGULAR Smith Fiberglass 48" 43" Hydrostatic-VPLT 1015 23" 0.00023 1046 0.003 Pass <br /> Dispenser Sump 1/2 Smith Fiberglass 22" 32" Hydrostatic-VPLT 1105 17' 0.07556 1121 1.799 Fail <br /> Dispenser Sump 314 Smith Fiberglass 22" 32" Hydrostatic-VPLT 1105 17' 0.06734 1121 1.788 Fail <br /> Dispenser Sump 5/6 Smith Fiberglass 22" 32" Hydrostatic-VPLT 1200 17" 0.06551 1216 1.764 Fail <br /> Dispenser Sump 7/8 Smith Fiberglass 22" 32" Hydrostatic-VPLT 1155 17" 0.06548 1211 1.701 Fail <br /> Comments: <br />