Laserfiche WebLink
Test Date: 09/13/2002 <br />r� <br />SECONDARY CONTAINMENT TEST RESULTS Work Order: 2223739 <br />c"use VC070 <br />Type <br />Tank or Disp <br /># <br />Manufacturer <br />Model or <br />Material <br />Diam./Width/Length <br />(") <br />Depth <br />(") <br />Test Method <br />Start <br />Time <br />Initial Level <br />Level Chane <br />Finish Final Pass/ <br />Time Result Fail <br />STP Sump <br />SUPREME <br />OPW <br />Fiberglass <br />48" <br />54" <br />Hydrostatic-VPLT <br />0621 <br />19" 0.10037 <br />0652 1.568 gph Fail <br />STP Sump <br />REGULAR <br />OPW <br />Fiberglass <br />48" <br />54" <br />Hydrostatic-VPLT <br />0620 <br />19" 0.00098 <br />0651 0.015 gph Pass <br />STP Sump <br />DIESEL <br />OPW <br />Fiberglass <br />48" <br />57" <br />Hydrostatic-VPLT <br />0709 <br />19" 0.07028 <br />0740 1.098 gph Fail <br />Dispenser Pan <br />7/8 <br />Bravo <br />Metal <br />18" <br />9" <br />Hydrostatic-VPLT <br />0553 <br />2" " 0.00001 <br />0609 0.001 gph Pass <br />Comments: Supreme sump has a leak around the vent/vapor line. The diesel sump has a leak around the product and or vent/vapor lines. <br />�J <br />