Laserfiche WebLink
,rw TankrXiogy <br />Test Date: 09/13/2002 <br />SECONDARY CONTAINMENT TEST RESULTS <br />Work Order: 2223739 <br />SIIMP TFSTS <br />Type <br />Tank or Disp <br /># <br />Manufacturer <br />Model or <br />Material <br />Diam./Width/Leng th <br />(" ) <br />Depth <br />(11 ) <br />Test Method <br />Start <br />Time <br />Initial <br />Level <br />Level <br />Chane <br />Finish <br />Time <br />Final <br />Result <br />Pass/ <br />Fail <br />STP Sump <br />SUPREME <br />OPW <br />Fiberglass <br />48" <br />54" <br />Hydrostatic-VPLT <br />0621 <br />19" <br />0.10037 <br />0652 <br />1.568 gph <br />Fail <br />STP Sump <br />REGULAR <br />OPW <br />Fiberglass <br />48" <br />54" <br />Hydrostatic-VPLT <br />0620 <br />19" " <br />0.00098 <br />0651 <br />0.015 gph <br />Pass <br />STP Sump <br />DIESEL <br />OPW <br />Fiberglass <br />48" <br />57" <br />Hydrostatic-VPLT <br />0709 <br />19" <br />0.07028 <br />0740 <br />1.098 gph <br />Fail <br />Dispenser Pan <br />7/8 <br />Bravo <br />Metal <br />18" <br />9" <br />Hydrostatic-VPLT <br />0553 <br />2" <br />0.00001 <br />0609 <br />0.001 gph <br />Pass <br />Comments: Supreme sump has a leak around the vent/vapor line. The diesel sump has a leak around the product and or vent/vapor lines. <br />C <br />n <br />