Laserfiche WebLink
a <br /> EMERGENCY PUM7 AND DWENSER SM OFF CHECKLIST <br /> FACILITY# 20 3 DATE -3-1-925 <br /> ADDRESS SL/,9-5 2 AQe .GLV®, <br /> r <br /> w <br /> T® <br /> 1. Authorize one dispenser of each product at the ARCOmatic. Go to dispenser of authorized <br /> product and turn on the handle. <br /> 2. Turn emergency switch, independent of ARCOmatic switch, to stop position. Note: each <br /> SM=encv stop switch must be tested independently. <br /> 3A. Tokheim Dispensers Only . <br /> Check relays in (1),power centers and (2) turbine relay boxes to verify that they are open and <br /> that power to the turbines is off. <br /> Open turbine sumps and verify turbines are off. Note results below. <br /> 3B. Gilbarco&Wayne Dispensers Only <br /> Verify at least one dispenser of each product will shut off. Check turbine relay boxes to verify <br /> that they are open and that power to the turbines is off. <br /> Open turbine sumps and verify turbines are off.Note results below. <br /> 4. ARCOmatic Sites Only:--(NCR's do not have emergency stop switches on console.) <br /> Authorize one dispenser to verify that dispenser power shuts down and/or turbine power shuts , <br /> down. Repeat procedure#4 for each dispenser and note results below. <br /> l <br /> STOP SWITCH SHUTS DOWN COMMENT/REPAIRS <br /> TURBINE DISPENSER <br /> (Y/N) (Y/N) <br /> ARCOmatic ` <br /> r <br /> OUTSIDE WALL <br /> INSIDE STORE k�k,(JC-(Z.-C a .- <br /> OTHER <br /> 5. Turn emergency switch back to run position. <br /> 6. Put station back in operation. <br /> 7. Install turbine circuit breaker and emergency stop decals supplied by ARCO if necessaty. <br /> CONTRACTOR a 0Vy- SIGNATURE `l m- Q LL- <br /> Comments: <br />