Laserfiche WebLink
19255517888 Main Fax GETTLER RYAN INC 03,42:09 p.m. 08-28-2007 11 !11 <br />Ease of installation • proper <br />positioningprotects iinvestment. <br />Sensor Detection Capabilities - Alarm Conditions <br />Fuel alarm is triggered when liquid reaches a nominal height of 1-1/2 inches. Sensor Out alarm is triggered when sensor is moved off <br />bottom of the pan/sump. <br />Operating Capabilities <br />• Operating temperature range: 0 to +60°C. <br />• Storage temperature range: -40 to +70°C. <br />• Sensor dimensions: 12" high, 2.2" diameter. <br />Sensor/Cable Length Configurations <br />• Position -Sensitive Sensor w/ 12 foot cable - Form Number 794380-323 <br />• 20' replacement cable with connector - Part Number 331102-001 <br />Sensor Interface Module <br />• TLS -350 Series Consoles (except TLS -350J) - interstitial Sensor Interface Module (Form Number 847490-102) accepts up to 8 sensors <br />(a maximum of 64 sensors could be monitored by the console). <br />• TIS -350J Console - 3 sensors max. <br />• TIS-300/PC-300 Series Consoles (no interface Module required) - 8 sensors max. <br />• ILS -350 Console - A Two -Wire Module (Form Number 845190-100) accepts up to 4 sensors (a maximum of 16 sensors could be <br />monitored by the console). <br />Console Software Compatibility <br />• All TLS -350 Series/TLS-300 Consoles <br />• All U -S-350 Consoles <br />Typical Posiiiion 5etitive Sensor Installat'an <br />Compatible Fuels <br />• Unleaded gasoline pump <br />Sensor Cord grip Weatherproof <br />p <br />• Leaded gasoline i a junction box <br />• Diesel t <br />Containment Seal -off <br />• Kerosene sump .—__1L <br />• Jet fuel 1/2" Rigid <br />conduit <br />• Aviation gasoline to console <br />• 5% methanol/95% unleaded <br />Brackets, clamp, etc. <br />• 15% ethanol/85% unleaded from optional Universal <br />t sensor mounting kit <br />• 15% MTBE/85% unleaded <br />Product line <br />IMPORTANTI Housing must compress <br />bottom the <br />position indicator against of <br />sump or you will have a 'Sensor Out alarm. <br />Incorrect Correct <br />For more information call <br />1.-888=581=7842 :' <br />l< 4 j � C © 2003 Weder-Root Company • 125 Powder Forest Drive • Simsbury, CT 06070 • USA <br />Y G Telephone: 860-651-2700 • Fax: 860.651-2719 • www.veeder.com <br />*Ael_ <br />VR 13784 PIN 0576047-081 Rev.A VRLP 7/2003 Printed in LISA <br />