Laserfiche WebLink
Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Spill Bucket Manufacturer ® Industry Standard ❑ ProfessionaI Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump Tester I Equipment Resolution: +/-0.002" <br />Bucket Diameter: <br />Bucket Depth: <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />Test Start Time: <br />Initial Reading (RI): <br />Test End Time: <br />Final Reading (RF): <br />Test Duration: <br />Change in Reading (RF -RI): <br />Pass/Fail Threshold or <br />Criteria: <br />Test Result: <br />Spill Box #87-2 fill <br />12" <br />10" <br />10 min. <br />9:35am <br />10:09am <br />4.4051 <br />4.4043 <br />9:50am <br />10:24am <br />4.4046 <br />4.4042 <br />15 min. <br />15 min. <br />-.0005 <br />-.0001 <br />+/-0.002" <br />X Pass ❑ Fail <br />Box #91 vapor <br />12" <br />10" <br />10 min. <br />9:35am <br />10:09am <br />5.1955 <br />6.1049 <br />9:50am <br />10:24am <br />5.1949 <br />6.1047 <br />15 min. <br />15 min. <br />-.0006 <br />-.0002 <br />+/-0.002" <br />X Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />* Installed new Vapor Bkt — 91 tank <br />* New drain — 87#2 fill bkt. <br />