Laserfiche WebLink
Line Leak Detector Test Data Sheet <br /> Station # Arco 2093 Date 8/30/2018 20 <br /> Address 3425 Tracy Blvd. Tracy ,CA 95376 <br /> Test Information <br /> 1 z 3 <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure(psi) 38 38 <br /> Line Bleed Back(ml) NA NA <br /> Trip Time(sec) NA NA <br /> Metering Pressure(psi) NA NA <br /> FIE Holding Pressure(psi) 34 32 <br /> Test Leak Rate(mllmin)(gph) 189ML 189ML <br /> PASS or FAIL pass pass <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical Ieak test detector test passtfail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler Ryan Inc <br /> Technician David Rouse Lir4220793 <br /> Signature <br />