bp <br /> RE09VED 9�� •.•.�� M <br /> Line Leak Detector Test Data Sheet ENVIRONMENTAL r i1®AP <br /> Station # Arco 2093 Date 9/06 2017 <br /> Address 3425 Tracy Blvd., Tracy, CA <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 8.7 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure(psi) 38 36 <br /> Line Bleed Back(ml) NA NA <br /> Trip Time(sec) NA NA <br /> Metering Pressure(psi) NA NA <br /> RE Holding Pressure(psi) 23 22 <br /> Test Leak Rate(ml/min)(gph) 18 9ML 18 9ML <br /> PASS or FAIL <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Gilbert Garcia Lic4220793 <br /> Signature <br />