Laserfiche WebLink
�� F—Dr omental Health Department <br /> SAN. JOAQUIN <br /> CULJ NTY SEP 1M?l <br /> Underground Storage Tank ProWpptspctlnt �iort <br /> Fatally name, FAMtj Addn»: FA ;ust <br /> ARCO 02093 3425 TRACY BLVD.TRACY 30.2018 <br /> SUMMARY OF VIOLATIONS <br /> tctwas R arcs IL w 1111101t-Valk.t.Camp" <br /> It m N Remartrs <br /> 308 CCR 2636(f)Failed to maintain a continuous monitoring system that activates an audible and visual alarm. <br /> The L11-Regular West STP sensor failed to activate an audible and visual alarm when tested to ensure continuous <br /> monitoring of the lank system. AN monitoring equipment shall be maintained to activate an audible and visual alar <br /> or slop the Dow of product at the dispenser when it detects a leak. The sensor was replaced and retested during the <br /> Inspection, A`UST Retrofit Verification with Inspector Already Onsite'form has been completed and provided to the <br /> operator and contractor. <br /> This was corrected on site. <br /> This Is a minor violation. <br /> 309 CCR 2636(Q(1)Monitming in sump I UDC failed to activate an audible and visual alarm or stop the flow product. <br /> The L11-Regular West STP sensor failed to activate an audible and visual alarm when tested to ensure continuous <br /> monitoring of the lank system. All morAoring equipment shelf be maintained to activate an audible,and visual alarm <br /> or stop the Row of product at the STP sump when it detects a leak. The sensor was replaced and retested during <br /> the Inspection by the service technician. <br /> This was corrected an site. <br /> This is a minor violation. <br /> 314 HSC 25290.1,2529x.2,25291 Failed to have so=dary con Or icry containment not tight. <br /> The 3/1412018 secondary containment test results indicate a failure at.ible T'nk ular pipe. All secondary <br /> containment for the UST system must be tighl. Immediately have a propd,and certified <br /> contractor repair or replace the failed component under permit and inspection of the <br /> This Is a minor violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the ENp with a statement <br /> documenting the corrective actions that have been or will be taken for each violation,and any supporting <br /> paperwork,by September 29th,2018. <br /> Document reviewed:Monitoring system certification test results 2015,2016,2017,secondary containment test <br /> results 2018,employee training,response plan,maintenance records,monitoring plan,financial responsibility <br /> documents and designated operator monthly inspection reports from September 7017-August 2018. <br /> Documents provided:Return to compliance c wfNication. <br /> Please be aware that as of January 1,2014,facility operators are required to upload the following UST program <br /> documents into the California Environmental Reporting System(CERS):UST Monitoring Site Plan,UST <br /> Certification of Financial Responsibility,UST Re once Plan,UST Letter from Chief Financial Officer if <br /> PAOM627 PM231416 8=1 06MM18 <br /> EHD 2"1 Mr,18►IMI r Far 4 of a unmegrWAM Simla TW*prorm OR <br /> 1868 E.Hazelton Avenue I Stockton,California 952051 T 208 468-31201 F 209 464-0138 1 www sjceruf.com <br />