Ask
<br />2008-03-25 17:19 SHELL R 1 IL 9253139090 >> P 7/12
<br />C
<br />UNDERGROUND STORAGE TANK
<br />RESPONSE PLAN - PAGE 2
<br />VI. LEAK INTERCEPTION AND DETECTION SYSTEM
<br />This information is required Qn!y for motor vehicle fuel UST systems constructed per the Alternate Construction Keyuirements of 23 CCR 02631, ;rid only if the Lcak
<br />Interception and Detection System (LIDS) does not meet the volumetric requirements of 23 CCR §2631(d)(1) through (5) (i.e., when accounting far rainfall and
<br />backfill material, the secondary containment volume is less than 100% of primary tank volume for a single UST; or in the case of multiple USTs in shared secondary
<br />containment. 150% orthe largest primary tank volume or 10°/u of aggregate primary tank volume, whichever is greater).
<br />ATTACH AN ADDITIONAL PAGE •I.O •frits PLAN O0N'rA1NfNG THE 170110WING INFORMATION:
<br />D The volume of the LIDS in rotation to the volume of the primary container;
<br />)o The amount of time the LIDS shall provide contuinn)cnl related to the time between detection of an unauthorized release and cleanup of the looked substance;
<br />> Tite depth from the bottom of the LIDS to the highcsl anticipated level of groundwater,
<br />Y The nature of the unsaturated soils under the LIDS mid their ability to absorb contaminants or to allow movement of contominmils;
<br />> The methods and scheduling for removal or all hazardous substulcu which may have been discharged from primary containment and are located in the
<br />unsaturated soils between the primary containment and groundwater, including the LIDS sump.
<br />VII. REPORTING AND RECORD KEEPING
<br />r —
<br />We will reporUrecord any overfill, spill, or unaulhori=d relcose tFom a UST system as indicated in this plkin.
<br />Recordnble Releases: Any unnuthorizod release from primary containment which the UST operator is able to clean up within eight (8) hours atter the release was
<br />detected or should reasonably have been detected, and which does not escape from secondary coniamtnctd, does not increase lite hazard of fire or explosion. and duos
<br />not cause any deterioration of secondary containment, must be recorded it) the facility's monitoring records. Monitoring records must include
<br />> The UST operator's name and telephone number;
<br />> A list of the types, quantities, and concentrations of hazardous substances released;
<br />> A description of the actions taken to control and clean up the release;
<br />'r• The method and location of disposal of the released hazardous substances, and whether a hazardous waste manifest was of wilt be used,
<br />> A description of uutions taken to repair the UST and to prevent future releasee;
<br />> A description of the method used h) reactivate interstitial monitoring after replacement or repair of primary containment.
<br />Reportable Releases: Any overfill, spill, or unauthorized release which cooMcs from secondary containment (or primary containment if no secondary containment
<br />exists), increases the hmrard of lire or explosion, or causes any deterioration of secondary containment, is a reportable release. Reportable releases are also recordable.
<br />Within 24 hours atter a reportable roloasc has been detected, or should have been detected, we will notify the local agency administering the UST program, or die
<br />release, investigate the release, and take immediate measures to stop the release. If necessary, or irrequired by the local agency, remaining stored product/waste will
<br />be removed from the UST to prevent further releases or facilitate corrective action. If an emergency exists, we will notify the stoic Unice of emergency Services.
<br />Within live (5) working days of a reportable release• we will Submit to the local agency a NO written report containing all of 4119 following information to tate extent
<br />that the information is known at the time or (tltng the report:
<br />> The UST owrnr's or operator's name and telephone number;
<br />b A list of the types, quantities, and concentrations of haznrdous materials released;
<br />> Tito approximate date or the release;
<br />> The date on whist the release was discovered;
<br />> The dote on which file release was stopped;
<br />> A description of actions taken In control and/or stop the roleosr•
<br />Y A description of corrective mid remedial actions, including investigations which were undertaken and will he conducted to determine the nature and extent of soil.
<br />ground water kir surlbce wader contamination due to the release;
<br />➢ 'rhe methods) of cleartup implemented to date, proposed cleanup actions, mid a schedule for implementing the proposed actions;
<br />> 'rhe method(s) ail location(s) of disposal of released hazardous materials and any contaminated soils• groundwater, or surface water,
<br />> Copies of any hazardous waste manifests used for off-site transport of hazardous wastes associated with clenn-nip nuivily;
<br />> A description of proposed methods fur any repair or replacement of UST system primary/secondary containment systems;
<br />> A description of additional actions taken to prevent future releases.
<br />We will follow the reporting procedures described above if any of the following conditions occur;
<br />> A recordable unauthorized release can not be: cleaned up or is still under investigation within eight (8) hours of detection;
<br />A Released hazardous; substances are discovered at the UST Site or in the surrounding area;
<br />> Unusual operating conditions are observed, including erratic behavior or product dispensing equipment, sudden loss of product, or the unexplained presence of
<br />weer in the tank, unless System equipment is found to he defective and is immediately repaired or replaced, and no leak has occurred;
<br />> Monitoring results from USI• system) monitoring equiptncnUmcthods indicate that a relense may have occurred, unless the moniluring equipment is found Io be
<br />dcfcetive and is immediately repaired, recalibrated, or replaced, kind additional monitoring does notconfirm the initial results.
<br />Record Rtleation: M tai coinq records mid written reports of unauthorized releases must be maintained on -sac (nr ofl=site at u readily available fixation, if approved
<br />by the local agency) fyf at iced 3 years. Hazardous waste shi 'ng/dispusal records (e.g.. manifests) must be maintained li)r at (cast 3 years from the date of shipment
<br />- VIII. U EMPERATOR SIGNATURE
<br />CERTIF► .ATIUN 1 rally (Blot diey4rmation pro ide herchi is true and accurate
<br />to the best of my knowledge.
<br />DATE R10
<br />OWNE Pr,RA1D .•1(' A'rURW
<br />March 20, 2008 .
<br />OWNER/01 TRATOR TITLE R7:
<br />PA/OPER OR NAME( int} n71
<br />Aura Sibley for Sell. 1 Products US
<br />HS&E; Compliance Coordinator
<br />(B,gemy Use Only) this pl C rCY1CWCd 8114; pproved Approved With Conditions nn Appr 4
<br />Local Agency Signature. _ Date
<br />111)CF 118'r -D (1=007) s
<br />
|