Laserfiche WebLink
ALLTEMI PETROLEUM SE CES <br /> 17759 Buttercup Circle, Sonora, CA 95370 <br /> (209) 532-7320/ Fax (209) 533-2650/indotten(oinlode.com <br /> California Tank l'ester: 98-1068 California Contractor:A 623541 <br /> ALERT UNDERFILL TANK TEST DATA SHEET <br /> Facility: Frank's One Stop Date: 11/18/97 <br /> Address: 2072 W. Yosemite <br /> City: Manteca, CA <br /> Facility contact: Frank Guinta <br /> (F2) Tank ID: West UL . Product: Unleaded Gallons: 10,000 <br /> Tank bottom: 130" Subtract lillpipe length: 35" = Tank Diameter: 95" <br /> Product level: 76" Tank water: 0" Backfill: 0" SGU: 0.730 <br /> Load cell: # 2 Serial: # 0220 Probe: 28 Powerlogger: 2 Battery: 9.65 vdc <br /> Probe weight: 91b. 5oz. = 4227 gams <br /> Subtract empty probe weight: - 1500 grams <br /> Ballast to add: =2727 grams <br /> Tank contains 8578 gallons = 86% full. (65%-9501o) Tare value: 54% <br /> Product pressure at tank bottom: 1.98 psi. <br /> Stabilization time from delivery to start of test: >2 hours. (1 hr. Minimum) <br /> Data collection began: 2130 hours 11/18 <br /> Data collection ended: 0730 hours 11/19 <br /> Total: 10.0 hours data collection. <br /> Quiet time began: 2300 hours 11/18 <br /> Quiet time ended: 0400 hours 11/19 <br /> Total: 5.0 hours quiet time. (2 hr. minimum) <br /> Filter bandwidth: 100 Disregard hours front: 5.0 Disregard hours rear: 2.85 <br /> Test time: 2.0 hours. (2 hr. minimum) <br /> Final Dv/D : 0.030 GPH. (see graph) ® Pass ❑ Fail <br /> Ulla ie test: Test Method: Alert 1050X (Vacuum) ® Pass ❑Fail <br /> Initial pressure: -1.50 j2si. Final pressure: -1.50 psi. (1.10 minimum) <br /> Remarks: <br /> e <br /> Test technician Mille Dotten, license#98-1068 �...a: . <br />