Laserfiche WebLink
• <br /> SWRCB,January 2002 II�i,Pagsf �f <br /> 4. TANK ANNULAR TESTING ` <br /> Test Method Developed By: X Tank Manufacturer ❑Industry Standard 1-1 Professional Engineer <br /> ❑Other(Sped) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Sped) <br /> i <br /> st Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: - ''/z"x-30"Hg. <br /> Tank#1&2 Tank#3 Tank# Tank# <br /> Is Tank Exempt From Testing?' No No <br /> Tank Capacity: 12K Split 6/6 12K <br /> Tank Material: Glass/Steel Glass/Steel <br /> Tank Manufacturer: Mosier Bros. Mosier Bros. <br /> Product Stored: Super 91/Diesel Regular 87 <br /> Wait time between applying 30 Minutes 30 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 10:25 10:35 <br /> Initial Reading(Rj): -10 Hg. -10 Hg. <br /> Test End Time: 11:25 11:35 <br /> Final Reading(RF): -10 Hg. -10 Hg. <br /> Test Duration: 1 Hour I Hour <br /> Change in Reading(RF-RI): 0 Hg. 0 Hg. <br /> Pass/Fail Threshold or Criteria: No Loss in Hg. No Loss in Hg. <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and Yes Yes <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)} <br />