0 <br /> SWRCB,January 2002 Pa L--2—Wk <br /> 7. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: E UDC Manufacturer 11 Industry Standard X Protes;s'i'ot3a'tl"tti4i�eet ,,,� <br /> El Other(Specify) <br /> Test Method Used: F-1 Pressure El Vacuum X Hydrostatic <br /> 11 Other(Specify) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> UDC#1&2 UDC#3&4 UDC#5&6 UDC#7&8 <br /> UDC Manufacturer: Bravo Bravo Bravo Bravo <br /> UDC Material: Coated Steel Coated Steel Coated Steel Coated Steel <br /> UDC Depth: 101, 10" 10" 101, <br /> Height from UDC Bottom to Top Enters from bottom Enters from bottom Enters from bottom Enters from bottom <br /> of Highest Piping Penetration: I <br /> Height from UDC Bottom to Enters from Bottom Enters from Bottom Enters from Bottom Enters from Bottom <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dry Dry Dry Dry <br /> testing: <br /> Portion of UDC TestedWater Line 7" Water Line 7" Water Line 7" Water Line 7" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both No No No No <br /> product and water)?* <br /> Turbine shutdown response time N/A N/A N/A N/A <br /> Is system programmed for fail- Yes Yes Yes Yes <br /> safe shutdown?* <br /> Was fail-safe verified to be No No No No <br /> operational?* <br /> Wait time between applying 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> water and starting test <br /> Test Start Time: 12:25 12:30 12:35 12:40 <br /> Initial Reading(Rj): .001 .001 .001 .001 <br /> Test End Time: 12:55 1:00 1:05 1:10 <br /> Final Reading(RF): .001 .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading(RF-R,): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Result: P iss Pass Pass Pass <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was Wsensor properly replaced and <br /> verified functional after testin ? L Yes Yes Yes Yes <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />