Laserfiche WebLink
JoThe Simmons Corporatict <br />MONTHLY <br />v� <br />a+STATISTICAL INVENTORYRECONCILIATION <br />Quik Stop Markets, Inc <br />P.O. Box 5745 <br />Fremont, CA 94537 <br />1. The tank owner is required to have an SIR report for each month. <br />2. Monthly reports must be submitted to the local agency upon request.. <br />3. The tank owner is required to have the report by the 20th day of the following month. <br />4. if for any reason, the test is neither "pass" nor "fail", the Inconclusive column will be marked. <br />5. The local agency may need to be notified of the tank that does not pass the SIR test within 24 hours of receipt of the report and the SIR report <br />should be submitted to the local agency within 10 days of the report. <br />6. Quantitative and Qualitative Methods: <br />a. A leak threshold, minimum detectable leak rate, and calculated leak rate must be provided for each tank. If not, then the tank failed the SIR test. <br />b. if the calculated leak rate for tank is greater than or equal to the leak threshold, the tank failed the SIR test. <br />c. If the minimum detectable leak rate for tank is greater than the certified performance standard (i.e., 0.1 or 0.2 gph) and the calculated leak rate <br />Is less than the leak threshold, the test Is inconclusive for that month. <br />d. Two consecutive failures and/or inconclusives may require a tank and/or piping integrity test within 15 days from the date of the <br />second report. The local agency should be contacted. <br />7. A conclusive result of "pass" or "fail" is required to meet monthly leak detection requirements. <br />Simmons Technician <br />I Date of SIR report: 05/12/97 <br />05/13/97 08:27:57 Page 1 <br />