Laserfiche WebLink
T_ riangle Environmental, Inc. <br />172 Hest Verdugo Ave., Burbank, CA 91502 <br />T E I LT -3 Hydrostatic Product Line Test Result Sheet <br />SITE- (34L SS'77�4e <br />DATE: <br />W/O # .7.295-r% <br />PRODUCT <br />START TIME <br />/READING <br />00:00/hL <br />END TIME <br />/READING <br />00:00/ML <br />TEST <br />PRESSURE <br />(psi) <br />VOLUME <br />RATE <br />(GPH) <br />RESULT <br />PASS/ <br />FAIL <br />32o <br />5 <br />16�s <br />16. <br />I certify that the above line tests were conducted on this <br />date according to the equipment manufacturer's procedures and <br />limitations and the results as listed are to my knowledge true and <br />correct. <br />Signature: OTTL# 2d -/O12 <br />Tech. �), Mfr's Cert. # Q�DIJ� <br />NOTE: <br />The test data collection time period must be fifteen minutes. <br />The test pass/fail is determined using a threshold of 190 ml <br />per hour (0.05 GPH) rate at 150% working pressure or 50 psi which <br />ever is less. The GPH rate is calculated as: ml/ 0.00106. <br />Copyright (c) Triangle Environmental,.Inc., March, 19 4111-L <br />