Laserfiche WebLink
a t <br /> Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00124 <br /> Tank#: 1 Work#: 12900921 <br /> Product: Unleaded Regular Test Date: 4/ 3/02 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: FX <br /> Product Level(in): L/D Serial#: 9234 <br /> Liquid Volume(Gals): Line Drain Back(ml): 62 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 30 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 2.9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: Test Method: TEI LT-3 <br /> Test End Time: Pump Brand: FE Petro <br /> Test Rate(gpi System Type: Pressure <br /> Test Result: N/A Line Pressure(psi): 50 <br /> EMENEEMENEEMLine Start Time: 2:15 PM <br /> Test Method: ULLAGE Line End Time: 2:30 PM <br /> UllageVolume(gals.): Line Start Level: 340 <br /> Ullage Test Time: Line End Level: 330 <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.011 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 2 <br />