Laserfiche WebLink
UNDER DISPL41SER CONTAINMENTODC) TESTING <br />Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: O Pressure O vacuum • Hydrostatic o Other (see below) <br />Measuring Equipment Used: INCON TS -STS (Electronic Sump Test System) <br />Descrintion Dian # 1/2 Dian # 3/4 <br />UDC manufacturer <br />Brave <br />Brave <br />UDC material <br />Steel <br />Steel <br />UDC depth (inches) <br />9 <br />9 <br />Height from UDC bottom to highest <br />piping penetration <br />Bottom <br />Bottom <br />Height from UDC bottom to lowest <br />electrical penetration <br />Bottom <br />Bottom <br />Condition of UDC prior to testing <br />Dry <br />Dry <br />Portion of UDC tested <br />Entire <br />Entire <br />Type of shut -down present <br />Float <br />Float <br />Was sensor removed for testing? <br />No <br />No <br />Was sensor properly replaced after testing? <br />Yes <br />Yes <br />Depth of water level from UDC bottom (in.) <br />6 <br />6 <br />Wait time for water level to stabilize (hr:min) <br />0:05 <br />0:05 <br />Test start time <br />10:04 AM <br />10:04 AM <br />Initial Probe Reading <br />0.2997 <br />0.2067 <br />Test end time <br />10:19 AM <br />10:19 AM <br />Final Probe Reading <br />0.2989 <br />0.2057 <br />Test duration (hr:min) <br />0:15 <br />0:15 <br />Change in water level (t 0.0000 inches) <br />-0.0008 <br />-0.0010 <br />Pass/Fail threshold (±0.0020 inches /; Hr.) <br />0.0020 <br />0.0020 <br />TEST RESULT <br />PASS <br />PASS <br />Comments: <br />0 2006 Walton Engineering, Inc. <br />