Laserfiche WebLink
SECONDARY LINE TESTING <br />Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: • Pressure O Vacuum o Hydrostatic o Other (see below) <br />Measuring Equipment Used: Pressure Gauge (range 0 to 15 psig) <br />Description Line #1 Line #2 Line #3 <br />Tank product <br />Gasoline - 89 <br />Gasoline - 87 <br />Gasoline - 91 <br />Pipe manufacturer <br />Ameron <br />Ameron <br />Ameron <br />Pipe material <br />FRP <br />FRP <br />FRP <br />Primary pipe diameter (inches) <br />2" <br />2" <br />2" <br />Secondary pipe diameter (inches) <br />3" <br />3" <br />Y <br />Method of secondary pipe isolation <br />Termination Boot <br />Termination Boot <br />Termination Boot <br />Location of secondary pipe isolation <br />Sump <br />Sump <br />Sump <br />Estimated length of piping run (feet) <br />45' <br />55' <br />65' <br />(include length of branch runs) <br />0.5 <br />0.5 <br />0.5 <br />Comments: <br />9 2004 Walton Engineering, Inc. <br />Wait time for pressure to stabilize (hr:min) <br />0:05 <br />0:07 <br />0:11 <br />Test start time <br />1:12 PM <br />1:15 PM <br />1:17 PM <br />Initial pressure (psig) <br />5.0 <br />5.0 <br />5.0 <br />Test end time <br />2:12 PM <br />2:15 PM <br />2:17 PM <br />Final pressure (psig) <br />5.0 <br />5.0 <br />5.0 <br />Test duration (hr:min) <br />1:00 <br />1:00 <br />1:00 <br />Change in pressure (psig) <br />0.0 <br />0.0 <br />0.0 <br />Pass/Fail threshold (psig) <br />0.5 <br />0.5 <br />0.5 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />Comments: <br />9 2004 Walton Engineering, Inc. <br />