UNDER DISPENSER CONTAINMENT (UDC) TEST "t - <br /> AUG 2 4 2016 <br /> EWRONMENTAL <br /> Test Method By: O Manufacturer • Industry Standard O Professionals �� ) <br /> Test Method Uses: O Pressure O vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#1/2 Disp#3/4 <br /> UDC manufacturer Brave Brave <br /> UDC material Steel Steel <br /> UDC depth (inches) 9 9 <br /> Height from UDC bottom to highest Bottom Bottom <br /> piping penetration <br /> Height from UDC bottom to lowest Bottom Bottom <br /> electrical penetration <br /> Condition of UDC prior to testing Dry Dry <br /> Portion of UDC tested Entire Entire <br /> Type of shut-down present Float Float <br /> Was sensor removed for testing? N/A N/A <br /> Was sensor properly replaced after testing? N/A N/A <br /> Depth of water level from UDC bottom (in.) 10 10 <br /> Wait time for water level to stabilize (hr:min) 0:05 0:05 <br /> Test start time 11:04 AM 11:04 AM <br /> Initial Probe Reading 1.0294 0.8307 <br /> Test end time 11:19 AM 11:19 AM <br /> Final Probe Reading 1.0294 0.8311 <br /> Test duration (hr:min) 0:15 0:15 <br /> Change in water level (±0.0000 inches) 0.0000 0.0004 <br /> Pass/Fail threshold (±0.0020 inches/;Hr.) 0.0020 0.0020 <br /> TEST RESULT PASS PASS <br /> Comments: <br /> 0 2016 Walton Engineering,Inc. <br />